A heat pump not heating properly, or blowing cool air, is not always broken. Heat pump air comes out at 90–100°F, which feels cooler than a furnace’s 130°F blast, and several times an hour in cold weather the unit runs a defrost cycle that briefly sends cool air through the vents. But if the house keeps getting colder, something needs attention. Work through these causes in order; the first five you can check yourself.
Heat pump not heating: is it actually a problem?
- Air feels lukewarm but the house holds temperature: normal.
- Cool air for 2–10 minutes, steam rising from the outdoor unit: defrost cycle. Normal.
- Cool air for more than 15 minutes and the house is cooling down: keep reading.
Measure it before you worry
A gas furnace pushes air at roughly 125°F; a heat pump typically delivers 90°F to 110°F and moves more of it. Your skin sits in the low 90s, so 95°F air blowing across your hand can feel cool even though it is far warmer than the room. Hold a kitchen or probe thermometer in a supply register for a few minutes before you assume something is broken.
| Register temperature in heat mode | What it likely means |
|---|---|
| 90°F to 110°F | Normal heat pump output |
| 80°F to 90°F | Possibly normal in very cold weather, or a sign of low airflow or low charge |
| Close to room temperature | Defrost, fan-only mode, or the compressor is not running |
| Colder than the room | System is in cooling mode or the reversing valve is stuck |
A commonly cited rule of thumb: supply air should be at least 20°F warmer than return air once the system has run for 10 minutes. If the gap is much smaller, keep reading.
1. Thermostat set to cool or fan “On”
Check that the thermostat is on Heat, the setpoint is above room temperature, and the fan is on Auto. With the fan on “On”, the blower keeps running between heating cycles and pushes room-temperature air that feels cold.
If the cold air started right after a thermostat swap, check the wiring. A heat pump thermostat needs the reversing valve wire (usually O or B, depending on the brand) set correctly; a thermostat configured for a furnace will run the system backwards. See our heat pump thermostat settings guide for the terminals.
2. Dirty air filter
A clogged filter cuts airflow across the indoor coil. The system overheats, trips a safety switch and stops heating. Replace the filter and restart the system.
3. Outdoor unit blocked by snow or ice
Some frost on the outdoor coil is normal and the defrost cycle clears it. A solid block of ice that stays for hours means defrost is failing or water is refreezing from a roof drip or poor drainage. Clear snow away by hand, turn the system to Emergency Heat to protect the compressor, and call for service if the ice returns. Never chip at the coil.
4. Tripped breaker or outdoor disconnect off
The outdoor unit and the indoor air handler are often on separate breakers. If the indoor fan runs but the outdoor unit is silent, check the breaker panel and the disconnect box next to the outdoor unit. If a breaker trips again right away, stop and call a technician.
5. Closed vents or blocked returns
Closing supply vents in unused rooms does not save energy with a heat pump. It lowers airflow and can cause the problems in cause 2. Keep at least 80% of vents open and return grilles clear of furniture.
6. Low refrigerant
A heat pump is a sealed system, so low refrigerant always means a leak. Symptoms include weak heat, ice on the refrigerant lines and a hissing sound. A technician needs to find and repair the leak, then recharge; that usually costs $100 to $600 or more.
7. Stuck reversing valve
If the heat pump blows cold air in heat mode and warm air in cool mode, the reversing valve or its solenoid may have failed. Replacing the valve is a major repair, typically $1,000 to $2,000, because the refrigerant has to be recovered and the valve brazed in.
8. Failed capacitor or contactor
If the outdoor fan or compressor hums but does not start, the start capacitor is a likely cause. It is one of the most common heat pump repairs and usually costs $100 to $250. Capacitors hold a dangerous charge even with the power off, so leave this to a technician.
9. It is simply too cold outside
Standard heat pumps lose capacity as the temperature drops. Below the “balance point”, often 25–35°F for older models, the heat pump alone cannot keep up and backup heat should switch on. If the backup heat strips have failed, the house slowly cools on very cold days. Modern cold-climate heat pumps keep most of their output down to 5°F.
If your system struggles in every cold snap, it may be undersized for your climate. Check the size your home needs with the heat pump size calculator.
Quick troubleshooting checklist
Work through these in order. The first six take minutes and cost nothing.
- Wait 15 minutes. If warm air returns, it was defrost.
- Confirm thermostat mode is Heat and the fan is on Auto.
- Raise the setpoint 3 to 5 degrees above room temperature.
- Replace the air filter.
- Check the breakers for both the indoor and outdoor units.
- Clear snow, leaves and debris from the outdoor unit.
- Measure supply and return air temperatures after 10 minutes of runtime.

Defrost mode: why it blows cool air for a few minutes
In cold, damp weather, frost builds up on the outdoor coil. The coil runs 10–20°F colder than the outdoor air, so frost can form even when it is in the 40s outside. To clear it, the heat pump briefly reverses into cooling mode and sends warm refrigerant to the outdoor coil. While that happens, your house gets little or no heat from the heat pump itself.
What normal defrost looks like
- The system checks for frost every 30–90 minutes in heating mode.
- Each cycle lasts about 5–15 minutes.
- The outdoor fan stops, and steam rises from the unit as the frost melts.
- You hear a click or a whoosh as the reversing valve switches.
- The thermostat may show “aux” heat. Many systems turn on backup heat so the vents do not blow cold air during defrost.
Signs defrost is not working
- Thick ice covers the whole outdoor coil and stays there for hours.
- Defrost runs much longer than 15 minutes, or starts over and over.
- The unit never goes into defrost even though the coil is iced.
These point to a bad defrost sensor or control board, low refrigerant, or a dirty coil. Do not chip ice off the coil. Switch to emergency heat and book a technician.

Emergency heat vs auxiliary heat
Auxiliary heat turns on automatically when the heat pump needs help: during defrost, when you raise the setpoint by several degrees, or on very cold days. It works alongside the heat pump.
Emergency heat is a setting you choose. It shuts the heat pump off completely and heats the house with backup heat only. Use it when the outdoor unit is damaged, iced solid or making alarming noises, until it can be repaired. Emergency heat usually runs on electric resistance strips, which cost two to three times as much per hour as the heat pump, so don’t leave it on longer than needed.
Running on emergency heat for days gets expensive. The heating cost calculator shows what electric resistance heat costs compared with the heat pump at your local rates.
Heat pump repair costs
Most heat pump repairs cost roughly $160–$660, and the average is about $400. Here is what the common fixes behind a heat pump not heating usually cost, parts and labor included:
| Repair | Typical cost |
|---|---|
| Thermostat repair or replacement | $80–$500 |
| Capacitor or contactor | $120–$400 |
| Outdoor fan motor | $200–$700 |
| Defrost control board | $200–$650 |
| Reversing valve | $200–$700 |
| Refrigerant leak repair | $200–$1,200, plus recharge |
| Compressor | $800–$3,500 |
After-hours and weekend calls cost more, so a problem that can wait a day on emergency heat is often cheaper to fix on a weekday. Regular heat pump maintenance catches weak capacitors and slow leaks before they leave you without heat.
When to call a technician
- A breaker trips repeatedly
- Ice covers the whole outdoor unit after a defrost cycle
- You hear grinding, screeching or loud buzzing
- Cool air lasts more than 15 minutes with the thermostat set correctly
- Air from the vents is colder than the room in heat mode
- The system turns on and off every few minutes
- Your electric bill jumps with no change in weather or use
Regular heat pump maintenance prevents most of these problems.
Worth having at home
As an Amazon Associate, HeatMath earns from qualifying purchases. These links open Amazon search results, so you can compare brands and prices yourself.
Frequently asked questions
How warm should the air from a heat pump feel?
Warm, but not hot. Heat pump supply air is usually about 85–110°F, below body temperature at the low end. A gas furnace blows air around 120–140°F, so a heat pump can feel cool by comparison even when it works fine. If the vents blow air close to room temperature for more than 15 minutes, something is wrong.
Should I turn off my heat pump if it is not heating?
Not right away. First check the thermostat mode, the filter and the breakers. If the outdoor unit is iced solid, making loud noises or not running at all, switch the thermostat to emergency heat. That shuts off the outdoor unit and keeps the house warm with backup heat until a technician arrives.
Is it worth repairing an old heat pump?
Small repairs such as a capacitor, contactor or thermostat are almost always worth it. A failed compressor or a major refrigerant leak on an older system is different: the repair can reach thousands of dollars. Compare that bill with the unit’s age and the price of a new system. Our guide on how long heat pumps last can help you decide.
Why does my heat pump blow cold air when I first turn it on?
The indoor coil needs a minute or two to warm up. If the fan starts before the coil is warm, the first air feels cool. It should warm up within a few minutes. If it does not, check the thermostat mode and fan setting.